1 setting battery test voltage, Setting battery test voltage, Figure 177: level 1 password access – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 123: Figure 178: setup menu, Figure 179: battery setup menu, Figure 180: set battery test voltage
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
107
1.
To enter Setup, use the default password <<<<<<<< (left arrow key eight times).
[Main Menu > SETUP]
POWER+ System Setup
Type in Level-1 PASSWORD, THEN – ENTER
Your privilege will expire after 15 min.
PASSWORD:________
Figure 177: Level 1 password access
2. Select
Battery:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service
Figure 178: Setup menu
8.10.1
Setting Battery Test Voltage
1. Select
Test-Voltage:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options
Figure 179: Battery setup menu
2.
Using the arrow keys, set the battery test voltage and press Ent:
[Main Menu > SETUP > (password) > Battery > Test Voltage]
BATTERY (TEST) VOLTAGE SETUP
VOLTAGE SETTING: 176.0V
Figure 180: Set battery test voltage