Table 13: log messages – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 102
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
86
Table 13: Log Messages
#
Message
Explanation
01
UPSMAJ
More than 1 UPS Module is sending an alarm or fault warning
02
UPSMIN
Single UPS Module is sending an alarm or fault warning
03
------ N.A.
04
------ N.A.
05
LOADBP
Load is now running on bypass. See Table 14 on page 87 to interpret
the LOADBP value.
06
VIBRA_
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to
avoid loading the log filling up.
07
OVTEMP Excess
temperature
08
OUTFLT
No AC output to load
09
BAT-HI
Excessive battery voltage
10
------ N.A.
11
BATEND
End of battery backup. Battery is discharged to shutdown limit
12
BATLOW
Low battery voltage
13
STSWRN
Static Switch Warning or alarm
14
E.P.O.
Emergency Power Off is active
15
EQ-HST
Battery is currently charging in equalizing mode, dc voltage is
temporarily increased
16
BATFLT
Batteries failed last test
17
USER-1
User 1 input open
18
USER-2
User 2 input open
19
USER-3
User 3 input open
20
AC-BRN
Input AC supply Brown Out
21
ACIN_H
AC input excessive
22
ACFAIL
AC input failure
23
STSWCM
Static Switch does not respond
24
SLFFLT
Last controller self-test failed
25
BAT-CB
Battery Circuit Breaker Open
26
CURSHR
Current Sharing fault, load current is not equally divided between
modules
27
UPSOUT
Fault (no current) in 1 or more output stage
28
UPSHDN
UPS shutdown by EPO, Battery Discharge, ON/OFF pressed