4. Select
Set AC Alarms Hysteresis:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT]
1> SET AC HIGH & LOW ALARM LEVELS
2> SET AC ALARMS HYSTERESIS
PLEASE SELECT 1
Figure 138: Ac alarms menu
5.
Use the arrow keys to set value, press Ent, and then Esc:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT > Set AC Alarms
Hysteresis]
SET AC VOLT ALARMS HYSTERESIS VALUE
(1 – 20) VOLT
05
Figure 139: Set ac voltage hysteresis
8.8.2
Setting Battery Floating Voltage Alarm
1. Select
FLOAT VOLT:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 140: Alarm set menu
2. Select
BATEND:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 141: Battery floating charge alarm setup menu