3 setting battery current limit, Setting battery current limit, Figure 183: battery setup menu – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 125: Figure 184: current limit setup menu, Figure 186: set current limit for (each) battery
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
109
8.10.3
Setting Battery Current Limit
1. Select
Current-Limit..:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options
Figure 183: Battery setup menu
2. Select
Current Limit Value Setup and press Ent:
[Main Menu > SETUP > (password) > Battery > Current Limit]
1> Current Limit Value Setup
2> Current Limit – Press to ENABLE
1
Press ‘2’ to Toggle Enable / Disable
Figure 184: Current Limit setup menu
3.
Select the current limit for each battery and press Ent:
[Main Menu > SETUP > (password) > Battery > Current Limit >Ent]
1> Set C. Limit of Battery #1 (99A)
Figure 185: Current limit indication for (each) battery
4.
Using the arrow keys, set the current limit for each battery. After the current limit is set
for all batteries, press Esc.
[Main Menu > SETUP > (password) > Battery > Current Limit >Ent > Ent]
CHARGE CURRENT LIMIT SETUP
CURRENT LIMIT: 99A
Figure 186: Set Current limit for (each) battery