2 power+ shutdown (switching to bypass), 3 power+ total shutdown (no ac output), Power+ shutdown (switching to bypass) – MaxPower Corp Gamatronic Power+ M50-RM User Manual
Page 84: Power+ total shutdown (no ac output), Figure 81: main screen – switching to bypass, Figure 82: bypass indication, Figure 83: main screen – total shutdown
Gamatronic Electronic Industries Ltd.
POWER+ RM
50
K
VA, N.Am. Std. – User Guide, Release 1.9
68
6.2
POWER+ Shutdown (Switching to Bypass)
1.
Switch the load OFF.
2.
Press twice on the On/Off button.
3.
Wait 2 minutes for the POWER+ to shut down. The control screen will indicate UPS OK
(OFF).
LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)
Figure 81: Main screen – switching to bypass
Note: This does NOT switch the entire POWER+ OFF. Power is still delivered to the load but in
bypass.
Figure 82: Bypass indication
6.3
POWER+ Total Shutdown (No Ac Output)
1.
Switch the load OFF.
2.
Press and hold the On/Off button for 10 seconds.
3.
The control screen will indicate UPS OK (OFF).
LOAD LEVEL ---23:14:40---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW Warning !