Troubleshooting

If in doubt concerning the troubleshooting procedures below, contact FlexLink.

Troubleshooting guide

Symptom

Cause

Corrective action

The elevator does
not start

Peripheral equipment is not
connected. Power not on,
emergency stop button pressed,
door not closed, no signal from
peripheral equipment or circuit
breaker tripped.

Only personnel with technical
knowledge or equivalent sufficient
experience may conduct the
following actions.

Check circuit-breakers.

Check that peripheral equip-
ment has started.

Check that the power is on.

Check that the emergency stop
button is not pressed.

Check that the door switch is
activated.

Press "Reset".

Check that peripheral equip-
ment produces signals.

Press "Start".

No products to discharge

Wait for products to arrive.

Foreign matter on photo-electric
cells

Clean photo-electric cells.

Products fasten/
have fastened

Photo-electric cell faulty, out of
position or dirty

Only personnel with technical
knowledge or equivalent sufficient
experience may perform the
following actions.

1

Clean photo-electric cells.

2

Adjust photo-electric cells.

3

Check photo-electric cells'

position and operation, and
that they are connected.