Installation and adjustment
Create
d
by EBCCW
0
0
:06
45
5112204
Instruction
1
Activate the reset button for more than 6 s to reach the operating
mode "Parameterization" - the green LED PWR flashes once. The
LEDs are switched off at intervals of 2 s for 0.3 s in the operating
mode "Parameterization" to differentiate from other operating
conditions.
2
Set the rated current of the drive with the 240° potentiometer, for
value see below. The four LEDs display the set current.
Current setting = 0.41 A: PWR=0, ERR=0, L=1, R=0.
3
Store the value by pressing the reset button again (retentive area
of the memory).
4
Actuate the Reset key for more than 2 s (and less than 6 s) to
display the set current for 3 s.
Communication interface
Integrator responsibility due to situation.
5.5.2
Field distributor
Apply to advanced elevator versions. Reference to electrical document.
Figure 21 Field distributor