4.3.4 Charger Module Control Interface Connector
The Charger Module Control Interface Connector is connected between
the charger module and ECM with Sense/Power leads connected to the APU
Output DC Bus. The interface control is a 4-pin (2x2 row) Universal Mini Mate-
N-Lok style male connector. See Fig. 4-1 for location.
Pin
Description
Function
1
Ignition Battery (+) Sense (YELLOW) wire.
Senses DC Charge on ignition
battery, adjusts charger for
correct voltage.
2
Inverter Battery (+) RED wire.
Input power to
charger module, operates on
36 or 48VDC battery packs to
charge ignition battery.
3
ECM Charger Control ORANGE
ECM Turns charger ON by
applying a LOW signal to this
pin (referenced to ignition
battery negative).
4
Inverter Battery NEGATIVE BLACK wire
NEGATIVE Input power to
charger module, operates on
36 or 48VDC battery packs to
charge ignition battery.
5($5
9,(:
-
4.3
Connectors, continued
Fig. 4-5 Charger Control Interface