3. Maintenance

39

031-132-B0-001 Rev. A

TM

©2000

3.2 Scheduled Maintenance, continued

3.2.3 ECM Self-Test Features, continued

Auto-Test Duration

The length of each Auto-test is measured in minutes. The default test

duration is 10 minutes. The test duration may be set between 10 and

120 minutes.

Manually enabling the Autotest feature

Switch SW5-8 is used to enable the autotest feature with a 14-day test

interval. The first autotest will begin 14 days from the time the ECM is

powered up with the configuration switch changed from 0 to 1 (OFF to

ON). To disable the autotest sequence, place switch SW5-8 in the OFF

position and restart the ECM. It is important to understand that upon

power up, the ECM looks for a change in the switch position before it

changes the test control parameters. (Please refer to ECM Manual, Alpha

p/n 744-862-C0)