3. Maintenance

46

031-132-B0-001 Rev. A

TM

©2000

3.7

Replacing Ignition Battery Charger Module Assembly

End of Procedure

Allow 15 minutes for completion of procedure

Tools required:

#2 Phillips screwdriver

Removal and replacement procedure:

1.

Locate and remove the charger module as shown below.

The charger module is located on the

outside of the APU housing, above the

generator run/stop switch mounting

bracket. Disconnect the connectors

from the front of the module.

Use the #2 Phillips screwdriver to

remove the two mounting screws from

the inside of the APU housing.

Slide the module out and replace with

new charger unit.