beautypg.com

Fig. 2-2, Generator set master switch, Fig. 2-3 – Alpha Technologies AlphaGen 5.0kW Auxiliary Power Unit User Manual

Page 30: Location of ecm run/auto/stop switch, Fig. 2-2 generator set master switch, Turn-up and test, 3 starting a local apu test, continued, 2 initial operation, continued

background image

2. Turn-Up and Test

30

031-132-B0-001 Rev. A

TM

©2000

2.2.3 Starting a Local APU Test, continued

2. Place generator set master switch to the middle (ECM) position.

CAUTION:

The Generator Control Board master switch will override

the Run/Auto/Stop (RAS) switch on the ECM. This

switch is normally left in the center, or "ECM" position.

(On older 5kW generators, the center position may be

marked 'Auto' or be blank.)

STOP

E
C
M

START

STOP

E
C
M

START

2.2

Initial Operation, continued

3.

Set RAS switch to “STOP”

4.

Verify Ignition Battery & AC Line Sense connection to ECM.

5.

Verify all alarms on ECM are OFF except Tamper Alarm & Auto
Mode Disabled.

6.

Remove gas port plug from input side of demand regulator, install
brass manometer port connection fitting and connect manometer to
fitting (Refer to fig. 3-1, and Section 3-17 for further details).

7.

Move RAS switch from “STOP to “AUTO”.

8.

Verify the engine starts within 3 salvo cycles per Table 1-1, Normal
Mode Crank Cycle.

9.

If engine fails to start within 3 salvo cycle and Engine Over Crank
isactivated, the gas line needs to be purged by removing air filter
and placing hand over the carbureator throat to choke while
cranking engine until engine starts.

10. Verify 11” of water column pressure is present at the input of the

demand regulator.

Fig.2-2

Generator set master switch

Fig. 2-3

Location of ECM Run/Auto/Stop switch