Page 29: Fig. 2-1 location of apu control board, Fig. 2-1, Location of apu control board, Turn-up and test

2. Turn-Up and Test
29
031-132-B0-001 Rev. A
TM
©2000
2.2.3 Starting a Local APU Test
Procedure:
1. Locate APU control board (mounted alongside the ECM).
2.2.2 Engine Lubrication
Check Engine lubrication Level Procedure:
Check the engine crankcase oil level. If necessary, add oil to fill it to
the FULL mark. DO NOT OVERFILL. Refer to the engine
manufacturers operators manual for proper fill capacities and oil
types. Ensure that the same brand of oil is used for topping the oil
level, as some oil manufacturers additives are not compatible with
each other. Never attempt to measure the oil level, or add oil, when
the engine is in operation.
CAUTION:
Do not attempt to crank or start the engine
before it has been serviced with the
recommended oil, or engine failure will result.
NOTE:
Refer to the Alpha 5 Generator OPERATORS manual
(p/n Tp-6076) provided by the manufacturer.
2.2
Initial Operation, continued
Generator Control Board
ECM
Fig. 2-1 Location of APU Control Board