Franklin Fueling Systems TS-TPI User Manual
Page 46

TROUBLESHOOTING
Page
8-3
8
TS-TPI Installation and Wiring Guide
STP-SCI or STP-SC
HEXVALUE
DECIMALVALUE
FAULT CODE DESCRIPTIONS
0
0
No Fault
1
1
Under Load (Dry Run or Tank Empty)
2
2
Under Voltage (low / fluctuating input voltage)
3
3
Locked Rotor
4
4
Open Circuit (or Locked Rotor or Relay Fault)
8
8
Uncalibrated (new installation)
9
9
Extended Run (continuous hook signal
greater than 60 minutes without pumping
product)
A
10
Relay Fault (relay contact failure)
Controller
Controller
Controller
Controller
Controller
STP-SCIII
HEXVALUE
DECIMALVALUE
FAULT CODE DESCRIPTIONS
0
0
No Fault
1
1
Under Load (Dry Run or Tank Empty)
2
2
Under Voltage (low / fluctuating input voltage)
3
3
Over Load / Locked Rotor
4
4
Open Circuit (or Locked Rotor or Relay Fault)
8
8
Uncalibrated (new installation)
9
9
Extended Run (continuous hook signal
greater than 60 minutes without pumping
product)
A
10
Relay Fault (relay contact failure)
B
11
L2 Open (L2 input leg not connected)
C
12
Over Voltage (voltage too high)
D
13
Voltage Unbalance Warning
E
14
Load Unbalance Warning
MagVFC
HEXVALUE
DECIMALVALUE
FAULT CODE DESCRIPTIONS
0
0
No Fault
1
1
Under Load (Dry Run or Tank Empty)
2
2
Under Voltage (low / fluctuating input voltage)
3
3
Locked Up (rotor locked)
4
4
Open Circuit
5
5
Ripple (capacitor bank bad)
6
6
Shorted (short circuit in connections)
7
7
Over Temp (excessive operating temperature)
8
8
Over Speed (excessive operating speed)
9
9
Extended Run
A
10
Locked rotor while PMA is running
E
14
Short Circuit (upper rail short)
Controller Type: VFCIV
Controller Type: VFCIV
Controller Type: VFCIV
Controller Type: VFCIV
Controller Type: VFCIV