beautypg.com

Franklin Fueling Systems TS-TPI User Manual

Page 46

background image

TROUBLESHOOTING

Page

8-3

8

TS-TPI Installation and Wiring Guide

STP-SCI or STP-SC

HEXVALUE

DECIMALVALUE

FAULT CODE DESCRIPTIONS

0

0

No Fault

1

1

Under Load (Dry Run or Tank Empty)

2

2

Under Voltage (low / fluctuating input voltage)

3

3

Locked Rotor

4

4

Open Circuit (or Locked Rotor or Relay Fault)

8

8

Uncalibrated (new installation)

9

9

Extended Run (continuous hook signal
greater than 60 minutes without pumping
product)

A

10

Relay Fault (relay contact failure)

Controller

Controller

Controller

Controller

Controller

STP-SCIII

HEXVALUE

DECIMALVALUE

FAULT CODE DESCRIPTIONS

0

0

No Fault

1

1

Under Load (Dry Run or Tank Empty)

2

2

Under Voltage (low / fluctuating input voltage)

3

3

Over Load / Locked Rotor

4

4

Open Circuit (or Locked Rotor or Relay Fault)

8

8

Uncalibrated (new installation)

9

9

Extended Run (continuous hook signal
greater than 60 minutes without pumping
product)

A

10

Relay Fault (relay contact failure)

B

11

L2 Open (L2 input leg not connected)

C

12

Over Voltage (voltage too high)

D

13

Voltage Unbalance Warning

E

14

Load Unbalance Warning

MagVFC

HEXVALUE

DECIMALVALUE

FAULT CODE DESCRIPTIONS

0

0

No Fault

1

1

Under Load (Dry Run or Tank Empty)

2

2

Under Voltage (low / fluctuating input voltage)

3

3

Locked Up (rotor locked)

4

4

Open Circuit

5

5

Ripple (capacitor bank bad)

6

6

Shorted (short circuit in connections)

7

7

Over Temp (excessive operating temperature)

8

8

Over Speed (excessive operating speed)

9

9

Extended Run

A

10

Locked rotor while PMA is running

E

14

Short Circuit (upper rail short)

Controller Type: VFCIV

Controller Type: VFCIV

Controller Type: VFCIV

Controller Type: VFCIV

Controller Type: VFCIV