Installation and Wiring

TS-TPI Installation and Wiring Guide

Stand AloneTS-TPI with Automatic Tank Gauge TS-1001 or

TS2001 and TPCs

Figure 2-5

Communication between ATG and TPCs, no additional ATG options required for full
operation

Stand Alone TS-TPI requires separate 120 - 240 vac, 50/60 hz, power

See Tank Sentinel Installation Guide for specific ATG instructions

TPCs that can be installed are MagVFC, IST-VFC, STP-SCI, STP-SC and STP-
SCIII. Available functions are limited on the IST-VFC, STP-SC and the STP-SCIII
controllers, see troubleshooting section for details

Connect TPCs so all Stand alone TPCs are on the same port and Master/Slave
configured units are on their own port. Address TPCs so controllers on same port
have unique addresses. If similar type stand alone TPCs are installed on the same
port as Master/Slave TPCs the stand alone TPCs will be seen as Slave units.

INPUTS

TS-LLD

485B

485A

S,RTN

DSY

IN 1

GND

IN 2

GND

TS1001 OR TS2001 ONLY

ATG

RED

BLACK

WHITE

BLACK

WHITE

RED

STAND ALONE TPI

T

X

D

485-

GN

D

RX

D 4

8

5

+

T

X

D

485

-

GN

D

RX

D 4

8

5

+

T

X

D

485

-

GN

D

RX

D 4

8

5

+

T

X

D

485

-

GN

D

RX

D 4

8

5

+

T

X

D

485

-

GN

D

RX

D 4

8

5

+

H

O

ST PO

R

T

PO

RT 1

PO

RT 2

POR

T

3

PO

RT 4

ADDITIONAL TPC
GROUPS

RE

D

WH

IT

E

BL

A

C

K

SEE TANK SENTINEL INSTALLATION GUIDE
(PART # 000-1050), THIS TPI USER'S GUIDE
AND APPROPRIATE
TPC INSTALLATION AND OWNER'S MANUAL
FOR COMPLETE WIRING INFORMATION

CABLE-BELDEN CONDUCTOR
#9365-18AWG OR EQUIVALENT

+ G

RS485

TPC

CONTROLLERS MAY INCLUDE THE
MagVFC, STP-SCI, STP-SCIII, VFC
AND STP-SC

ADDITIONAL
TPC CONNECTIONS

RED
WHITE

BLACK

GND L2/N

L1

INPUT POWER

120 -240 Vac 50/60 hz

TS-TPI
RESET

TPC FAULT
RESET

ALARM
SILENCE