beautypg.com

6ts-tpi data and reports – Franklin Fueling Systems TS-TPI User Manual

Page 32

background image

TS-TPI DATA AND REPORTS

Page

6-1

6

TS-TPI Installation and Wiring Guide

6

TS-TPI DATA AND REPORTS

Overview

The INCON Tank Sentinel displays, prints and faxes data and report information for

the user. This chapter describes the DISPLAY and DIAG (Diagnostic) menus, that

feature comprehensive user-interface data and report functions.

TPI Status Display Notes

The Display function allows a user to view current information from pump controllers

on a real time basis. The TPI periodically collects data from each pump controller.

The Tank Sentinel, in turn, periodically collects the data from the TPI and stores it

internally. The Tank Sentinel Display interface allows this data to be viewed at any

time.

To access the Display function, the user first presses the MENU key and then

DISPLAY key. Amongst the option keys displayed, the user must select the PUMPS,

which will cause a list of the attached pump controllers to be presented. Once the

user selects a pump, the console will proceed to display the real time data for that

pump controller.

See Appendix A at the back of this manual for Status Code definitions and Pump

Controller Fault Code definitions.

Tank Sentinel Keypad & Menu Navigation

Character input/editing:

Use UP or DOWN keys to display more menus- (MORE) or selections (UP/DN)

Press the CANCEL key to cancel data entry

Use the ENTER key to accept data entry

Press menu keys (M1 to M4) to access menus.

Press M4 to backspace (delete) one or more characters to the left

Use M2 to move the cursor right

Press M1 to move the cursor left