Controller type: vfc – Franklin Fueling Systems TS-TPI User Manual

Page 45

background image

8

Page

8-2

TROUBLESHOOTING

TS-TPI Installation and Wiring Guide

Status Codes

During normal operation

21 TPC is ready to run, no hook signal is detected, and low priority

31 TPC is ready to run, a hook signal is detected, and low priority

61 TPC is ready to run, no hook signal is detected, and priority

71 TPC is ready to run, a hook signal is detected, and priority

See chapter 3 “Level management” for details on “priority” and “low priority.”

If the Status code is an even number this indicates the TPC is not detected by the TS-TPI. This

indicates a communication problem between the TS-TPI and the TPC.

If the last digit is greater than 8, the TPC is in an alarm condition. See the Fault code on ATG

display and compare it with the table for the particular model controller in use or see the

troubleshooting guide in the Installation and Owner’s manual for the specific TPC.

If the last digit is 5 the TPC is in calibration mode

If the last digit is 3 the controller needs help (master/slave and alternating configurations only)

For specific code interperatation please contact INCON Technical Support.

Fault Codes

Fault codes vary based on controllers in service. Reading only the least significant digit refer to the
table for the particular TPC in use.

IST-VFC

HEX VALUE

DECIMALVALUE FAULT CODE DESCRIPTIONS

0

0

No Fault

1

1

Under Load (Dry Run or Tank Empty)

2

2

Under Voltage (low / fluctuating input voltage)

3

3

Locked Up (rotor locked)

4

4

Open Circuit (IST-VFC motor)

5

5

Ripple (capacitor bank bad)

6

6

Shorted (short circuit in connections)

7

7

Over Temp (excessive operating temperature)

Controller Type: VFC

Controller Type: VFC

Controller Type: VFC

Controller Type: VFC

Controller Type: VFC