Ls300 – Franklin Fueling Systems TS-TPI User Manual

Page 10

background image

2

Page

2-4

Installation and Wiring

TS-TPI Installation and Wiring Guide

LS300

TPI BOARD

BLACK

WHITE

RED

TXD 485-

GND

RXD 485+

TXD 485-

GND

RXD 485+

TXD 485-

GND

RXD 485+

TXD 485-

GND

RXD 485+

TXD 485-

GND

RXD 485+

HOST PORT

PORT 1

PORT 2

PORT 3

PORT 4

NO TS-TPI BOARD IN THIS LS300
IF TS-TPI IS PRESENT, REMOVE IT BEFORE
MAKING THE RS232 CONNECTION

LS300

EXTERNAL
RS232 PORT

TS1001 OR TS2001 ONLY

ATG

INPUTS

TS-LLD

485B

485A

S,RTN

DSY

IN 1

GND

IN 2

GND

RED

BLACK

WHITE

CABLE-BELDEN
3 CONDUCTOR
#9365-18AWG
OR EQUIVALENT

SEE TANK SENTINEL INSTALLATION GUIDE
(PART # 000-1050) AND LS300 USER'S GUIDE
(PART # 000-0040) FOR COMPLETE ATG AND
LS300 WIRING INFORMATION

PURCHASE
RS232 CABLE
LOCALLY

TS-TPI / two TS-LS300 with Automatic Tank Gauge

TS-1001, TS2001

Figure 2-3

Provides communication between ATG and both TS-LS300 consoles. ATG
requires the Line Leak detection option for full operation of TS-LS300 and ATG
communication.

Only one TS-LS300 has TS-TPI installed, if both have a TPI board remove the TPI
from one of the TS-LS300

The RS232 cable is supplied by the customer

TS-TPI configuration switch SW1 pole 3 is ON. See Figure 2-7 for more details and
switch settings on TS-TPI