Pulsar Controller Status
Display
Millennium Controller
Status Display
Rect/
Conv
LEDs
Dist.
Module
LED
Possible Problem(s)
Possible Solution(s)
MIN Thermal Probe
Fail
Norm
green
green
Battery thermal probe failed.
1. Ensure thermal probe is properly connected to thermal probe
cable.
2. Ensure cable is properly connected to the rear of the
Distribution Module.
3. If problem persists, replace thermal probe.
4. If problem still persists, call your local field representative.
No response
Fail
red
blink
red
blink
Controller failure, all devices on the
communication bus reporting loss
of communication with controller.
1. Check controller to ensure it is properly inserted into its slot. If
so, perform the following steps:
2. Remove the controller input power connector for 1 minute
and then reset.
3. If problem persists, replace controller with new controller
board.
4. If problem still persists, call your local field representative.
MIN Minor
Communication Fail
Fail
red
blink
(one
rect)
green
Rectifier lost communication with
controller.
1. Reset the rectifier by removing the rectifier, waiting
approximately 30 seconds, and replacing.
2. If problem persists, replace the rectifier.
3. If problem still persists, call your local field representative.
Norm
green
green
Rectifier removed from a running
system, but not uninstalled.
Issue the Menu > Control / Operations > Uninstall Equipment
command for any rectifier that was removed.