Connect batteries, Tray mounted batteries, Battery disconnect switch connection – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual
Page 29: Figure 37 battery disconnect switch, Figure 38 batt disconnect switch input bus, Figure 39 battery cable -48v

NE-M
Installation Guide
H5692448
CC848815325 r06 May 2013
29
Connect Batteries
Tray Mounted Batteries
Go to the procedure for the disconnect method provided on the trays:
• Battery Disconnect Switch Connection
• Anderson Connector Connection
• Direct to Battery Bus Connection
Battery cables from factory mounted battery trays are factory installed and terminated to the distribution panel.
Battery Disconnect Switch Connection
Step
Action
1
Ensure disconnect switch is in the OFF position
(downward) prior to making any connections.
Remove the two 6/32 screws to remove the
plastic cover.
Figure 37 Battery Disconnect Switch
2
Connect one end of the 2/0 cable to the input bus
of the disconnect switch with 1/4-20 hex nuts
provided.
Torque to 65 in-lb – 7/16” socket.
Figure 38 Batt Disconnect Switch Input Bus
3
Re-attach clear plastic cover to disconnect
switch and secure with 6-32 screws.
4
Connect Battery Cable (hot side)
48V Battery Strings
Connect the 2/0 cable between the V- post of the
left-most battery and the input bus of the
disconnect switch.
Torque to battery manufacturer’s specification.
Figure 39 Battery Cable -48V
Disconnect
Switch
Input Bus