Installation, Preparation, Safety – GE Industrial Solutions H5692448 Power Systems Infinity M1 (NE-M) User Manual
Page 16: Installation tools, Equipment identification, Anchor frame, Floor mounted frame

NE-M
Installation Guide
H5692448
CC848815325 r06 May 2013
16
Installation
Follow all site engineering instructions. This section is provided only as a guide.
Preparation
Safety
Read and follow all safety statements, warnings, and precautions in the Safety section of this manual and manuals of
all other equipment before installing, maintaining or repairing the equipment.
Installation Tools
You will need the following tools.
• Wire cutters and strippers
• Heat shrink gun
• 5/16-inch (8 mm) hex driver
• Digital meter with an accuracy of ±0.02%
• Screw drivers (flat-blade and Phillips)
• ESD wrist strap
• 24 or 48V test load
• Calibrated clamp-on dc current meter (0.1 ADC
sensitivity)
• Torque wrench
• Socket wrenches:
• 7/16” and 9/16” - cable connections
• 19 mm - anchor bolts
• 12" extension for socket
• Masonry drill kit as required
• Compression for installation of various
compression lugs
• Protective canvas
• Insulating rubber mat
• Standard insulated installation tools, screwdrivers,
etc.
• Controller Manual
Galaxy Pulsar Plus Family Product Manual
or
Galaxy Millennium II Installation and User’s Guide
• Windows-based personal computer laptop (PC)
and cable to connect the PC communications port
to the local port of the controller or a CAT5 LAN
cable. (Optional. See the controller manual for
more information).
Equipment Identification
Identify the equipment you have received. Follow procedural steps which match the equipment being installed.
Anchor Frame
Ventilation space is required to the rear of the equipment: 4” to solid surface, 6” to heat producing surface.
Floor Mounted Frame
Using the 847135688 Floor Anchor Kit (recommended):
Anchor Type (Hilti)
Wrench
Torque
(4) 12 mm Cap Bolts
19 mm
720 in-lb
60 ft-lb
82 Nm
Note: For systems with tray mounted batteries at sites requiring Seismic Zone 4 rating, (2) 847135688 kits are required
to provide (8) floor anchors.
Note: If using Equivalent Floor Anchors, make sure the floor anchors are rated for this application.