Converting from Previous Models

Section 2-12

7.

Turn OFF the power to the PLC and return the Ethernet Unit's rotary
switches for the node address to its original setting.

8.

Turn ON the power to the PLC.

Converting from ETN21 Mode to ETN11 Mode

1.

Turn OFF the power to the PLC, and set the Ethernet Unit's rotary switches
for the node address as follows:

2.

Turn ON the power to the PLC. The Unit's indicators will change as follows:

3.

Set the rotary switches for the node address to 0F. There will be no change
to the indicators.

4.

Set the rotary switches for the node address to FF. The RUN indicator will
begin to flash.

5.

Set the rotary switches for the node address to 0F. The Unit mode change
function will start, and the ERH indicator will flash for approximately five
seconds.

6.

After the mode has been changed, the indicators will appear as shown be-
low, depending on whether the change was completed normally or if an er-
ror occurred.

• If the Mode Change was Completed Normally

• If an Error Occurred in the Mode Change

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

-

-

Lit

Not lit

Not lit

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

0

0

Not lit

Not lit

Not lit

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

0

0

Not lit

Lit

Not lit

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

0

F

Not lit

Lit

Not lit

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

F

F

Flashing

Lit

Not lit

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

0

F

Flashing

Lit

Flashing

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

0

F

Flashing

Lit

Lit

Node address

Indicators

Ч

16

1

Ч

16

0

RUN

ERC

ERH

0

F

Flashing

Lit

Not lit