Communicating between OMRON PLCs

Section 6-6

CX-Programmer's Unit Setup

Setup Tab

FINS/TCP Tab

Not set. (All defaults are used.)

FinsGateway ETN_UNIT Setup

TCP Nodes Tab: Ethernet Node Definition Dialog Box

6-6

Communicating between OMRON PLCs

FINS commands can be sent from the user’s ladder-diagram program in the
PLC by using the SEND(090), RECV(098), and CMND(490) instructions.

SEND(090): Writes I/O data from the local node to another node.
RECV(098): Reads I/O data from another node to the local node.
CMND(490): Issues FINS commands for controlling operations such as send-
ing and receiving I/O memory data to and from other nodes, reading informa-
tion regarding other nodes, and so on.

6-6-1

Communications Specifications

The following table shows the specifications for PLC communications using
the SEND(090), RECV(098), and CMND(490) instructions.

Item

Setting

Broadcast

All ones (4.3BSD)

FINS/TCP port

Default (9600)

IP address

0.0.0.0 (Use default IP address.)

Subnet mask

0.0.0.0

Baud rate

Automatic detection

IP router tables

None

Item

Setting

Node address

2

IP address

192.168.250.2

Destination port number

9600

Keep-alive setting

Selected (yes)

Item

Specifications

Destination

1:1

SEND(090), RECV(098), CMND(490) instructions

1:N

SEND(090), CMND(490) instructions (broadcasting)

Data length

SEND(090):
990 words (1,980 bytes) max.; broadcasting: 727 words (1,454
bytes)
RECV(098):
990 words (1,980 bytes) max.
CMND(490):
1,990 bytes max.; broadcasting: 1,462 bytes (after FINS com-
mand code)