Omron CS1W-ETN21 User Manual
Page 83
58
Converting from Previous Models
Section 2-12
■
Manipulating the Rotary Switches for the Node Address with a Precision
Screwdriver
Converting from ETN11 Mode to ETN21 Mode
1.
Turn OFF the power to the PLC, and set the Ethernet Unit's rotary switches
for the node address as follows:
2.
Turn ON the power to the PLC. The Unit's indicators will change as follows:
3.
Set the rotary switches for the node address to 01. There will be no change
to the indicators.
4.
Set the rotary switches for the node address to F1. The RUN indicator will
begin to flash.
5.
Set the rotary switches for the node address to 01. The Unit mode change
function will start, and the ERH indicator will flash for approximately five
seconds.
6.
After the mode has been changed, the indicators will appear as shown be-
low, depending on whether the change was completed normally or if an er-
ror occurred.
• If the Mode Change was Completed Normally
• If an Error Occurred in the Mode Change
Note
If an error occurs in the mode change, remove the Ethernet Unit,
create the I/O tables, and correct the settings using the procedures
described in this section.
Node address
Indicators
Ч
16
1
Ч
6
0
RUN
ERC
ERH
0
0
Not lit
Not lit
Not lit
Node address
Indicators
Ч
16
1
Ч
16
0
RUN
ERC
ERH
0
0
Not lit
Lit
Not lit
Node address
Indicators
Ч
6
1
Ч
16
0
RUN
ERC
ERH
0
1
Not lit
Lit
Not lit
Node address
Indicators
Ч
16
1
Ч
16
0
RUN
ERC
ERH
F
1
Flashing
Lit
Not lit
Node address
Indicators
Ч
16
1
Ч
16
0
RUN
ERC
ERH
0
1
Flashing
Lit
Flashing
Node address
Indicators
Ч
16
1
Ч
16
0
RUN
ERC
ERH
0
1
Flashing
Lit
Lit
Node address
Indicators
Ч
16
1
Ч
16
0
RUN
ERC
ERH
0
1
Flashing
Lit
Not lit