Using FINS Applications
Section 6-5
■
System Configuration Example 2: Using Routing Tables
In this example, an online connection is made via the Ethernet to a PLC on a
Controller Link network (PLC 3 below) from a CX-Programmer/CX-Integrator
connected to the Ethernet network.
Conditions
• FINS/UDP method
• IP address conversion: Automatic generation method (dynamic)
CX-Programmer's Change PLC Dialog Box
CX-Programmer's Unit Setup
Setup Tab
Same as for System Configuration Example 1.
Routing Table Settings and Transfer to Each PLC
Set the routing tables with CX-Integrator, and transfer them.
1.
Using CX-Integrator, connect online, and select Routing table
−
Settings.
Then create FINS local routing tables (a local network table and a relay
network table).
Example: PLC 1 Routing Table Settings
Settings for target PLC (PLC3)'s Change PLC Dialog Box
Setting
PLC name
PLC3
Network classification
Ethernet
Network Tab
FINS destination
FINS transmission
source address
1
Network number
2
Node address
3
Frame length
2,000 bytes
Response monitor time
2 seconds
Driver Tab
Workstation node address
1
Automatic generation method
Not selected
IP address
192.168.250.2
(Ethernet Unit IP
address)
Port number
9600
CX-Programmer/CX-Integrator
Ethernet port
Node address: 1
IP address: 192.168.250.1
Ethernet (network address 1)
Routing
according to
routing table
Controller
Link Unit
Ethernet Unit
IP address conversion: Automatic generation method (dynamic)
Gateway between networks
PLC1
Controller Link Unit
Target PLC
Controller Link Unit
Node address 2
Node address 3
Controller Link (network address 2)
PLC2
PLC3
Ethernet Unit node address: 2
Ethernet Unit IP address: 192.168.250.2
Ethernet Unit unit number: 0
Controller Link Unit node address: 1
Controller Link Unit unit number: 1
Routing to final network address 2
requires relaying through node
address 2 of relay network address
1 (Ethernet Unit).