Using FINS Applications

Section 6-5

System Configuration Example 2: Using Routing Tables

In this example, an online connection is made via the Ethernet to a PLC on a
Controller Link network (PLC 3 below) from a CX-Programmer/CX-Integrator
connected to the Ethernet network.

Conditions

• FINS/UDP method

• IP address conversion: Automatic generation method (dynamic)

CX-Programmer's Change PLC Dialog Box

CX-Programmer's Unit Setup

Setup Tab

Same as for System Configuration Example 1.

Routing Table Settings and Transfer to Each PLC

Set the routing tables with CX-Integrator, and transfer them.

1.

Using CX-Integrator, connect online, and select Routing table

Settings.

Then create FINS local routing tables (a local network table and a relay
network table).

Example: PLC 1 Routing Table Settings

Settings for target PLC (PLC3)'s Change PLC Dialog Box

Setting

PLC name

PLC3

Network classification

Ethernet

Network Tab

FINS destination

FINS transmission
source address

1

Network number

2

Node address

3

Frame length

2,000 bytes

Response monitor time

2 seconds

Driver Tab

Workstation node address

1

Automatic generation method

Not selected

IP address

192.168.250.2
(Ethernet Unit IP
address)

Port number

9600

CX-Programmer/CX-Integrator

Ethernet port

Node address: 1
IP address: 192.168.250.1

Ethernet (network address 1)

Routing
according to
routing table

Controller
Link Unit

Ethernet Unit
IP address conversion: Automatic generation method (dynamic)

Gateway between networks
PLC1

Controller Link Unit

Target PLC

Controller Link Unit

Node address 2

Node address 3

Controller Link (network address 2)

PLC2

PLC3

Ethernet Unit node address: 2
Ethernet Unit IP address: 192.168.250.2
Ethernet Unit unit number: 0
Controller Link Unit node address: 1
Controller Link Unit unit number: 1

Routing to final network address 2
requires relaying through node
address 2 of relay network address
1 (Ethernet Unit).