3 error log, Error log – Omron CS1W-ETN21 User Manual
Page 227
202
Error Log
Section 8-3
8-3
Error Log
The Ethernet Unit provides an error log that records errors that have occurred
during Ethernet Unit operation. The contents of the error log can be read or
cleared from a Programming Device, such as the CX-Programmer, or it can
be read or cleared using FINS commands from a workstation or computer.
(See 7-3-7 ERROR LOG READ and 7-3-8 ERROR LOG CLEAR).
Logged Errors
The following errors are recorded in the error log.
• Errors in network operation
• Errors in data transfers
• Error in the CPU Unit
5
DNS server error
ON
Unit
ON when the following errors occur during DNS server
operation:
• An illegal server IP address is set.
• A timeout occurs during communications with the
server.
OFF
Unit
OFF when DNS server operation is normal.
6
Routing table error
ON
Unit
ON if the routing table information is incorrect.
OFF
Unit
OFF when the routing table is normal.
7 to 10
(Not used.)
---
---
---
11
SNTP server error
ON
Unit
ON when the following errors occur during SNTP server
operation:
• An illegal server IP address or host name is set.
• A timeout occurs during communications with the
server.
OFF
Unit
OFF when SNTP server operation is normal.
12
SMTP server error
ON
Unit
ON when the following errors occur during SMTP server
operation:
• An illegal server IP address or host name is set.
• A timeout occurs during communications with the
server.
• The verification time from the server has expired (when
POP before SMTP is set).
OFF
Unit
OFF when SMTP server operation is normal.
13
POP server error
ON
Unit
ON when the following errors occur during POP server
operation:
• An illegal server IP address or host name is set.
• A server verification error (user name or password)
occurs.
• A timeout occurs during communications with the
server.
OFF
Unit
OFF when use of the POP server is normal.
14
Address disagreement
ON
Unit
ON if the remote IP address is set to automatic genera-
tion but the local IP address host number and FINS
node address do not agree.
OFF
Unit
OFF under all other circumstances.
15
EEPROM error
ON
Unit
ON if an error has occurred in the EEPROM memory.
OFF
Unit
OFF when the EEPROM memory is normal.
Bit
Error
Status
Manipulated by
Unit operation