Web function password, Using the web function (setting password) – Omron CS1W-ETN21 User Manual
Page 270
![background image](/manuals/203937/270/background.png)
245
Ethernet Unit Web Function
Appendix G
Status Monitor
Web Function Password
To prevent unauthorized access to the Ethernet Unit from a Web browser, password entry is required to enable
display and setting of the parameters. Even if the password has not been set, the default password “ETHER-
NET” must be entered. To change this password, set a new password in the HTTP Tab of the CX-Program-
mer’s Unit Setup, or use the Web function and select Settings - IP address and Protocols - HTTP.
Note 1.
Setting a new Web function password as soon as possible is recommended to prevent unauthorized
access.
2.
The Web function can also be disabled by setting in the Web function option.
Using the Web Function (Setting Password)
The Ethernet Unit’s Web window is displayed by accessing the following URL from the Web browser.
URL: http://(Ethernet Unit’s IP address)/0
Use the following procedure to set the Unit’s system settings (HTTP password setting in this example) using
Internet Explorer version 6.0 and the Ethernet Unit’s Web function.
Receive Mail
Unit Setup window- Receive Mail Tab
Mail Address Protection Setting
Unit Setup window- Receive Mail Tab - Protect using mail address
Attached File Enable Settings
Unit Setup window- Receive Mail Tab - Receive file with specified extension only
Command Enable Setting
Unit Setup window- Receive Mail Tab - Receive specified commands only
Menu item
Corresponding CX-Programmer function
Status View
---
Unit information
FINS(0501): CONTROLLER DATA READ
Unit status
FINS(0601): CONTROLLER STATUS READ
Protocol status
---
IP status
FINS(2762): PROTOCOL STATUS READ, IP status
ICMP status
FINS(2762): PROTOCOL STATUS READ, ICMP status
TCP status
FINS(2762): PROTOCOL STATUS READ, TCP status
UDP status
FINS(2762): PROTOCOL STATUS READ, UDP status
Memory status
FINS(2763): MEMORY STATUS READ
Socket status
FINS(2764): SOCKET STATUS READ
Fins status
Ethernet Unit’s internal node table
Mail log
RECEIVE MAIL: READ MAIL LOG
Error log
FINS(2102): READ ERROR LOG
Send mail status
Mail send status 1 to 8
Menu item
Parameter item
Corresponding CX-Programmer function