2 switch settings, Switch settings, Cs-series ethernet units – Omron CS1W-ETN21 User Manual
Page 56: 2-1 cs-series ethernet units
31
Switch Settings
Section 2-2
2-2
Switch Settings
2-2-1
CS-series Ethernet Units
Setting the Unit Number
The unit number is used to identify individual CPU Bus Units when more than
one CPU Bus Unit is mounted to the same PLC. Use a small screwdriver to
make the setting, taking care not to damage the rotary switch. The unit num-
ber is factory-set to 0.
Note
(1) Turn OFF the power supply before setting the unit number.
(2) If the unit number is being set for the first time or changed, then I/O tables
must be created for the PLC.
(3) With CS-series and CJ-series PLCs, words are automatically allocated in
the CIO Area and DM Area according to the unit numbers that are set.
For details, refer to SECTION 4 Ethernet Unit Memory Allocations.
Setting the Node Address
With the FINS communications service, when there are multiple Ethernet
Units connected to the Ethernet network, the Ethernet Units are identified by
node addresses. Use the node address switches (NODE NO.) to set the node
address between 01 and FE hexadecimal (1 to 254 decimal). Do not set a
number that has already been set for another node on the same network.
The left switch sets the sixteens digit (most significant digit) and the right
switch sets the ones digit (least significant digit). The node address is factory-
set to 01.
Note
Turn OFF the power supply before setting the node address.
Relation to IP Addresses
When using the automatic generation method (either dynamic or passive) for
address conversion, set the rightmost byte of the IP address set for the Ether-
net Unit to the same value as the node address. If this is not possible, either
the IP address table method or the combined method must be used for
address conversion. (For details, refer to 5-2 IP Addresses in FINS Communi-
cations.) If the FINS communications service is not used on the Ethernet net-
work, then it is all right to overlap with other Ethernet Units. The setting,
however, must be made within a range of 01 to FE. If a value outside of this
range is set, the ERC indicator will light.
Unit Operating Mode
Change Function
If the node address is set to 00, the Unit operating mode change function will
start.
This function changes the format for the Unit Setup (in the CPU Bus Unit Sys-
tem Setup Area) when converting to a CS1W-ETN21 or CJ1W-ETN21 Ether-
net Unit from one of the previous models (CS1W-ETN01/11 or CJ1W-ET11).
For details, refer to 2-12 Converting from Previous Models.
Setting range:
0 to F
Setting range:
01 to FE (1 to 254 decimal)
Ч
16
1
Ч
16
0