beautypg.com

Response codes – Omron CS1W-ETN21 User Manual

Page 204

background image

179

Command/Response Reference

Section 7-3

Response Block

Results Storage Format

Parameters

Socket Option (Command)

The socket option specified as 1 byte. The setting is not valid for this com-
mand. Set to 0.

TCP Socket Number
(Command)

The TCP socket number to send the data specified as 1 byte between 1 and
8.

Results Storage Area
(Command)

The area in which the results of the command execution are stored. The first
byte specifies the memory area and data type (variable type). The 2nd to 4th
bytes specify the beginning address of the results storage area. Refer to
page 158 for details about the variable types and addresses that can be spec-
ified.

Number of Bytes Sent
(Command, Results
Storage Area)

The number of bytes in the data sent specified between 0 and 1,984. The
results storage area stores the actual number of bytes sent.

Data Sent (Command)

Specifies the data to be sent.

Response Codes

27 13

Command

code

Response

code

Number of

bytes sent

Response

code

Response code

Description

0000

Normal

0105

Local IP address setting error

0302

CPU Unit error; execution not possible.

1001

Command too large

1002

Command too small

1003

The number of bytes sent does not match the amount of data.

1100

The TCP socket number or number of bytes sent is out of
range.

1101

The variable type for the results storage area is out of range.

1103

Non-zero bit address specified for the results storage area.

220F

The specified socket is sending data.

2210

No connection could be established to the specified socket.

2211