beautypg.com

Appendix f inspections, Inspections, Appendix f – Omron CS1W-ETN21 User Manual

Page 266: Items, Tools required for inspection, Inspection interval, Inspection items, Standard tools, Tools required under special circumstances

background image

241

Appendix F

Inspections

Carry out regular inspections to ensure the Ethernet Unit is functioning perfectly.

Items

Most of the parts that make up an Ethernet Unit are semiconductor components. None of the parts in the Unit
will wear out after a specific lifetime, but some parts may deteriorate due to extreme operating condition.
Therefore, it is important to inspect the Unit regularly.

Inspection Interval

Normally inspect once or twice per year. Choose the inspection period according to the severity of the operat-
ing conditions. New installation should be inspected more frequently until they are judged to be stable.

Inspection Items

Correct any of the items in the table below not conforming to the specified standard.

Tools Required for Inspection

The following tools are needed to inspect the Ethernet Unit:

Standard Tools

• Flat-blade and Phillips screwdrivers

• Tester or digital voltmeter

• Industrial alcohol and a clean cloth

Tools Required Under Special Circumstances

• Synchroscope

• Pen oscilloscope

• Thermometer and hygrometer

Item

Details

Standard

Environment

Temperature around Unit

0 to 55

°

C

Humidity around Unit

10% to 90% (with no condensation)

Accumulated dust

No accumulated dust

Mounting

Ethernet Unit firmly attached

No looseness

Transceiver cable connector fully pushed in

No looseness

Condition of transceiver cable

No visible abnormality

Twisted-pair cable connector fully pushed in

No looseness

Condition of twisted-pair cable

No visible abnormality