Response codes – Omron CS1W-ETN21 User Manual

Page 195

background image

170

Command/Response Reference

Section 7-3

Command Block

Response Block

Results Storage Format

Parameters

Socket Option (Command)

The socket option specified as 1 byte. The setting is not valid for this com-
mand. Set to 0.

UDP Socket Number
(Command)

The UDP socket number to send the data specified as 1 byte between 1 and
8.

Results Storage Area
(Command)

The area in which the result of the command execution is stored. The first byte
specifies the memory area and data type (variable type). The 2nd to 4th bytes
specify the beginning address of the results storage area. Refer to page 158
for details about the variable types and addresses that can be specified.

Destination IP Address
(Command)

The IP address of the node to which data is being sent is specified in hexa-
decimal.

Destination UDP Port
Number (Command)

The UDP port number of the node to which data is being sent.

Number of Bytes Sent
(Command, Results
Storage Area)

The number of bytes in the data sent by this command. Up to 1,984 bytes can
be specified, or up to 1,472 bytes can be specified if the broadcast address is
specified as the send destination. The results storage area stores the actual
number of bytes sent.

Send Data (Command)

Specifies the data sent to the remote node.

Response Codes

Destination

UDP

port number

Number of

bytes sent

Destination IP address

Command

code

Socket option

UDP socket number

27 03

Results storage area

1984 bytes max.

Send data

Response

code

Command

code

27 03

Number of

bytes sent

Response

code

Response code

Description

0000

Normal

0105

Local IP address setting error

0302

CPU Unit error; execution not possible.

1001

Command too large

1002

Command too small

1003

The number of bytes sent does not match the sent data
length.