206

Error Log

Section 8-3

03C2

FINS/TCP packet discarded

01 to 10:

Connection
number

02:
Reopened
because
remote node
closed

03:
Reopened
because of
reception
error

04:
Reopened
because of
transmission
error

05:
Reopened
because RST
received from
remote node

06:
Reopened
because of
no keep-alive
response

Have the FINS/TCP connection
status checked when a
SEND(090), RECV(098), or
CMND(490) instruction is exe-
cuted in the ladder program.

---

07: Illegal
FINS/TCP
procedure

Refer to Operation Manual, Con-
struction of Applications: SEC-
TION 7
, and correct the remote
node (application on a personal
computer).

---

08: Insuffi-
cient mem-
ory during
server pro-
cessing

09: Insuffi-
cient mem-
ory during
client pro-
cessing

0A: Insuffi-
cient mem-
ory during
node switch-
ing

There is too much load (traffic) on
the Ethernet Unit. Correct the sys-
tem so that traffic is not concen-
trated.

---

03C3

FINS/UDP packet discarded

00

01 to FE:
Transmission
source node
address

The automatic generation (static)
method was used as the IP
address conversion method, so
remote IP address information in
internal memory could not be
changed.

---

Error

code

Meaning

Detailed error code

Correction

EE-

PROM

1st byte

2nd byte