Troubleshooting Procedures

Section 8-4

8-4-6

Network Connection Problems

Is the LNK indicator

lit?

Did all nodes

fail to respond to ping

command?

Is the twisted-pair

cable secured?

E

N

D

Firmly secure the cable.

Power may not be being supplied to the hub.

Y

N

Y

N

N

Did a particular

node fail to respond to

ping command?

The remote node may not support ICMP.

Y

N

Is the remote

node functioning as an

FTP client?

Y

N

Y

Only SD indicator
is flashing.

Connect by FTP.

Is the twisted-pair

cable between the Ethernet Unit

and the hub straight

cable?

Use straight cable.

N

Y

Network connection problem occurred.

Go through the procedure in
Startup Problems before
starting this procedure.

Execute the ping
command for all nodes
connected to the network.

Replace first the twisted-pair cable, then the hub,

and then the Ethernet Unit, in order.

The twisted-pair cable for that node may be

disconnected.

Execute FINS PROTOCOL
STATUS READ.

If the following parameters are counted, the corresponding

communications services may not be possible with the remote
node.
[IP status]

(2) (3) (5) (6) (All communications services)

[ICMP status] (5) (6) (7) (8) (ping)
[TCP status]

(3) reception status (4) (5) (6) (FTP, TCP sockets)

[UDP status]

(1) (2) (3) (FINS communications, UDP socket)

If the following parameters are counted, the load at the Ethernet

Unit may be too high. Adjust the user applications.
[IP status]

(4) (8) (9)