Network connection problems, 4-6 network connection problems – Omron CS1W-ETN21 User Manual
Page 244
219
Troubleshooting Procedures
Section 8-4
8-4-6
Network Connection Problems
Is the LNK indicator
lit?
Did all nodes
fail to respond to ping
command?
Is the twisted-pair
cable secured?
E
N
D
•
Firmly secure the cable.
•
Power may not be being supplied to the hub.
Y
N
Y
N
N
Did a particular
node fail to respond to
ping command?
•
The remote node may not support ICMP.
Y
N
Is the remote
node functioning as an
FTP client?
Y
N
Y
Only SD indicator
is flashing.
•
Connect by FTP.
Is the twisted-pair
cable between the Ethernet Unit
and the hub straight
cable?
•
Use straight cable.
N
Y
Network connection problem occurred.
Go through the procedure in
Startup Problems before
starting this procedure.
Execute the ping
command for all nodes
connected to the network.
•
Replace first the twisted-pair cable, then the hub,
and then the Ethernet Unit, in order.
•
The twisted-pair cable for that node may be
disconnected.
Execute FINS PROTOCOL
STATUS READ.
•
If the following parameters are counted, the corresponding
communications services may not be possible with the remote
node.
[IP status]
(2) (3) (5) (6) (All communications services)
[ICMP status] (5) (6) (7) (8) (ping)
[TCP status]
(3) reception status (4) (5) (6) (FTP, TCP sockets)
[UDP status]
(1) (2) (3) (FINS communications, UDP socket)
•
If the following parameters are counted, the load at the Ethernet
Unit may be too high. Adjust the user applications.
[IP status]
(4) (8) (9)