IP Addresses in FINS Communications

Section 5-2

applications, such as mail servers, are normally allocated fixed IP addresses.
Ethernet Units in PLC systems are also allocated fixed IP addresses.

Simultaneously Running Multiple Applications on a Personal Computer

In communications involving previous models, multiple communications appli-
cations were configured on personal computers according to data accessing
uses, and the fact that no more than one UDP port number for FINS commu-
nications could be used on any given computer created a problem. This
Ethernet Unit provides a practical solution with an internal table that pairs
remote nodes (applications) with FINS node addresses, enabling dynamic
changes.

FINS/UDP
Communications Method

FINS nodes are allocated individually for each application on the computer,
and the respective FINS/UDP port numbers that are used are also allocated
individually. When FINS/UDP FINS commands are sent from individual appli-
cations to the Ethernet Unit, the respective remote IP addresses and remote
port numbers in the internal table are dynamically changed.

FINS/TCP
Communications Method

With this method as well, FINS nodes are allocated individually for each appli-
cation on the computer, and the respective FINS/TCP port numbers that are
used are also allocated individually. Each application is positioned with a
FINS/TCP client, and requests the opening of a connection with the Ethernet
Unit's FINS/TCP server. When the connection is established, the respective
remote IP address and remote port number in the internal table are dynami-
cally changed.

5-2-4

Related Products and Communications/Setting Methods

Models Supporting Automatic Generation Method (Dynamic)

Product

Model/Series/

Version

Supports automatic

generation method

(dynamic)?

CS-series Ethernet
Unit

100BASE-TX

CS1W-ETN21

Yes

10BASE-5

CS1W-ETN01

No: Set by automatic
generation method or
combined method. Com-
munications are not pos-
sible with personal
computers with variable
IP addresses.

10BASE-T

CS1W-ETN11

CJ-series Ethernet
Unit

100BASE-TX

CJ1W-ETN21

Yes

10BASE-T

CJ1W-ETN11

No: Set by automatic
generation method or
combined method. Com-
munications are not pos-
sible with personal
computers with variable
IP addresses.

CV/CVM1-series
Ethernet Unit

10BASE-5

CV500-ETN01

FinsGateway

Version 4.xx or
lower

Version 2003 or
higher

Yes

Programmable Terminal

NS Series

No: Set manually so that
automatic settings can be
used with the automatic
generation method.

Open Network Controller (ONC)

---