beautypg.com

Ethernet unit with a global address, 3-3 ethernet unit with a global address – Omron CS1W-ETN21 User Manual

Page 136

background image

111

Private and Global Addresses

Section 5-3

5-3-3

Ethernet Unit with a Global Address

Conditions for Using
Communications
Applications

Communications applications can be used over the Internet under the follow-
ing conditions:

1,2,3...

1.

FINS Communications Service

• A device such as a personal computer (with a FINS application including

a CX-Programmer) can connect online and communicate over the Inter-
net with an Ethernet Unit that has a global address.

• FINS/TCP is recommended as the FINS communications service

method.
FINS/TCP is more reliable than FINS/UDP in terms of communications
errors involving IP routers.

• The IP address table method is used as the Ethernet Unit's IP address

conversion method.

• The TCP port number to be used for FINS/TCP cannot be used if prohib-

ited by a firewall in the communications path.

2.

Transferring Files

• Files can be transferred over the Internet between a device such as a per-

sonal computer (i.e., an FTP client) and a PLC with an Ethernet Unit that
has a global address.

• The TCP port number to be used for FTP cannot be used if prohibited by

a firewall in the communications path.

Intranet

CX-Programmer, etc.
FINS/TCP client computer

Ethernet

Communications
over Internet

Firewall

IP router

Internet

Global address
(required)

Intranet

IP router

Firewall

Private address

Global address

Communications
in intranet

Ethernet

PLC

Ethernet Unit: Global address

Private address

Private address

Not output to Internet