Converting from Previous Models

Section 2-12

If the format change is from ETN11 mode to ETN21 mode, then there will be
no effect on previous applications. If the change is from ETN21 mode to
ETN11 mode, however, then certain limitations will go into effect.

The following table shows the limitations that apply when operating in ETN11
mode.

Note

(1) These limitations do not apply when the CPU Bus Unit System Setup

Area format is in ETN21 mode.

(2) When I/O tables are created using one of the new Ethernet Unit models,

the CPU Bus Unit System Setup Area format is in ETN21 mode from the
beginning.

Item

Specifications in

ETN11

mode

Baud rate

• Automatic detection (100Base-TX or

10Base-T)

FINS node address setting range

• 1 to 254

IP address conversion: Automatic
generation method

• Dynamic only

TCP keep-alive

• No time setting (Uses default setting)

FINS/TCP

• Server only for all connections (Uses default

setting)

TCP socket services

• Socket option (keep-alive setting): Yes
• Number of Bytes Received at TCP Socket

Nos. 1 to 8: Yes

• Data Received Flag: Yes

FTP server function

• Port No. setting: No (Uses default setting)

Mail send function

• The specifications for previous Units apply.
• The mail transmission status is as follows:

• Status of user mail transmission

Status

of transmission condition setting 5

• Status of periodic mail transmission

Sta-

tus of transmission condition setting 6

• Status of mail transmission when error

occurs

Status of transmission condition

setting 7

Mail receive function

• Cannot be used

Automatic clock adjustment function

• Cannot be used

DNS server host name

• Cannot be used