184
Command/Response Reference
Section 7-3
Remote TCP Port Number
(Response)
Specifies the TCP port number for the remote node.
TCP Transitions
(Response)
Specifies the TCP connection status using the following numbers.
For details on TCP status changes, refer to Appendix C TCP Status Transi-
tions.
Response Codes
7-3-21 IP ADDRESS TABLE WRITE
Writes the IP address table.
Command Block
Response Block
Parameters
Number of Records
(Command)
The number of records to write is specified in hexadecimal between 0000 and
0020 (0 to 32 decimal) in the command. If this value is set to 0, the IP address
table will be cleared so that no records are registered.
Number
Status
Meaning
00000000
CLOSED
Connection closed.
00000001
LISTEN
Waiting for connection.
00000002
SYN SENT
SYN sent in active status.
00000003
SYN RECEIVED
SYN received and sent.
00000004
ESTABLISHED
Already established.
00000005
CLOSE WAIT
FIN received and waiting for completion.
00000006
FIN WAIT 1
Completed and FIN sent.
00000007
CLOSING
Completed and exchanged FIN. Awaiting ACK.
00000008
LAST ACK
FIN sent and completed. Awaiting ACK.
00000009
FIN WAIT 2
Completed and ACK received. Awaiting FIN.
0000000A
TIME WAIT
After closing, pauses twice the maximum seg-
ment life (2MSL).
Response code
Description
0000
Normal
0105
Node address setting error
Local IP address setting error
0302
CPU Unit error; execution not possible.
1001
Command too large
1002
Command too small
1100
Connection number not set from 1 to 16
Number
of records
IP address
table records
Command
code
27 50
IP address
table records
6 bytes
6 bytes
Command
code
Response
code
27 50