126

Using FINS Applications

Section 6-5

6-5

Using FINS Applications

6-5-1

CX-Programmer (CX-Server)

The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.

System Configuration Example 1: No Routing

In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.

Conditions

• FINS/UDP method

• IP address conversion: Automatic generation method (dynamic)

CX-Programmer's Change PLC Dialog Box

CX-Programmer/CX-Integrator

Ethernet (Network address: None)

Ethernet port

Target: PLC1

Ethernet Unit

IP address: 192.168.250.1

FINS/UDP method

Node number: 1

IP address conversion: Automatic
generation method (dynamic)

Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2

Settings for target PLC (PLC1)'s Change PLC Dialog Box

Setting

PLC name

PLC1

Network classification

Ethernet

Network Tab

FINS transmission source address

0

FINS destination

Network number

0

Node address

2

Frame length

2,000 bytes

Response monitor time

2 seconds

Driver Tab

Workstation node address

1

Automatic generation method

Not selected

IP address

192.168.250.2
(Ethernet Unit IP
address)

Port number

9600