Using FINS Applications
Section 6-5
6-5
Using FINS Applications
6-5-1
CX-Programmer (CX-Server)
The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.
■
System Configuration Example 1: No Routing
In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.
Conditions
• FINS/UDP method
• IP address conversion: Automatic generation method (dynamic)
CX-Programmer's Change PLC Dialog Box
CX-Programmer/CX-Integrator
Ethernet (Network address: None)
Ethernet port
Target: PLC1
Ethernet Unit
IP address: 192.168.250.1
FINS/UDP method
Node number: 1
IP address conversion: Automatic
generation method (dynamic)
Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2
Settings for target PLC (PLC1)'s Change PLC Dialog Box
Setting
PLC name
PLC1
Network classification
Ethernet
Network Tab
FINS transmission source address
0
FINS destination
Network number
0
Node address
2
Frame length
2,000 bytes
Response monitor time
2 seconds
Driver Tab
Workstation node address
1
Automatic generation method
Not selected
IP address
192.168.250.2
(Ethernet Unit IP
address)
Port number
9600