4 network installation, Network installation, Basic installation precautions – Omron CS1W-ETN21 User Manual

Page 59: 4-1 basic installation precautions

background image

34

Network Installation

Section 2-4

The CJ1W-ETN21 Ethernet Unit’s maximum current consumption is 370 mA.
Make sure that the total current consumption of all the Units connected to the
same CPU Backplane or Expansion Backplane does not exceed the output
capacity of the Power Supply Unit.

2-4

Network Installation

2-4-1

Basic Installation Precautions

• Take the greatest care when installing the Ethernet System, being sure to

follow ISO 8802-3 specifications. You must obtain a copy of these specifi-
cations and be sure you understand them before attempting to install an
Ethernet System. Unless you are already experienced in installing com-
munications systems, we strongly recommend that you employ a profes-
sional to install your system.

• Do not install Ethernet equipment near sources of noise. If noise-prone

environments are unavoidable, be sure to take adequate measures
against noise interference, such as installing network components in
grounded metal cases, using optical links in the system, etc.

C
P
U

P
S

I

C

P
S

I
I

P
S

I
I

P
S

I
I

CPU Rack

10 Units max.

End cover

10 Units max.

End cover

Expansion Backplane

10 Units max.

End cover

Expansion Backplane

10 Units max.

End cover

Expansion Backplane

Up to four Ethernet
Units can be mounted.

PS: Power Supply Unit
CPU: CPU Unit
IC: I/O Control Unit
II: I/O Interface Unit