Cj-series ethernet units, Unit no, Node no. × 16 – Omron CS1W-ETN21 User Manual

Page 57: 2-2 cj-series ethernet units

background image

32

Switch Settings

Section 2-2

2-2-2

CJ-series Ethernet Units

Setting the Unit Number

The unit number is used to identify individual CPU Bus Units when more than
one CPU Bus Unit is mounted to the same PLC. Use a small screwdriver to
make the setting, taking care not to damage the rotary switch. The unit num-
ber is factory-set to 0.

Note

(1) Turn OFF the power supply before setting the unit number.

(2) If the unit number is being set for the first time or changed, then I/O tables

must be created for the PLC.

(3) With CS-series and CJ-series PLCs, dedicated areas are automatically

allocated in the CIO Area and DM Area according to the unit numbers that
are set. For details, refer to SECTION 4 Ethernet Unit Memory Alloca-
tions
.

Setting the Node Address

With the FINS communications service, when there are multiple Ethernet
Units connected to the Ethernet network, the Ethernet Units are identified by
node addresses. Use the node address switches to set the node address
between 01 and FE hexadecimal (1 to 254 decimal). Do not set a number that
has already been set for another node on the same network.

The top switch sets the sixteens digit (most significant digit) and the bottom
switch sets the ones digit (least significant digit). The node address is factory-
set to 01.

Note

Turn OFF the power supply before setting the node address.

Relation to IP Addresses

When using the automatic generation method (either dynamic or passive) for
address conversion, set the rightmost byte of the IP address set for the Ether-
net Unit to the same value as the node address. If this is not possible, either
the IP address table method or the combined method must be used for
address conversion. (For details, refer to 5-2 IP Addresses in FINS Communi-
cations
.) If the FINS communications service is not used on the Ethernet net-
work, then it is all right to overlap with other Ethernet Units. The setting,
however, must be made within a range of 01 to FE. If a value outside of this
range is set, the ERC indicator will light.

01

23456789

ABCD

EF

UNIT
No.

Setting range:

0 to F

01

23456789

ABCD

EF

NODE
No.

×

16

1

01

23456789

ABCD

EF

×

16

0

Setting range:

01 to FE (1 to 254 decimal)