7-18 Troubleshooting
On-screen
message
Description
Action
BB Temp2 Alm 02
A low temperature alarm
is detected in base board.
BB Temp2 Alm 09
A high temperature alarm
is detected in base board.
BB Temp1 Alm 02
A low temperature alarm
is detected in base board.
BB Temp1 Alm 09
A high temperature alarm
is detected in base board.
1. Check if fans in Module Enclosure work
normally.
2. Refer to the User’s Guide of the Module
Enclosure to make sure that the sufficient
number of fans are installed in correct
locations.
3. Check if the fans and modular servers are
installed in correct locations.
4. Check if the ambient temperature of
installation location satisfies the operation
guarantee condition.
5. Take one of the following measures to
reboot (reset) the modular server.
* Issue an OS command.
* Press Ctrl + Alt + Del.
* Issue a command from Web browser of
EXPRESSSCOPE Engine or NEC
ESMPRO Manager.
6. Take one of the following measures to power
off the modular server and then on.
* Power off the modular server from OS,
then press the POWER/SLEEP switch to
power on.
* Press the POWER/SLEEP switch to power
off the modular server, then press it again
to power on.
* Issue a command from Web browser of
EXPRESSSCOPE Engine or NEC
ESMPRO Manager.
7. Power off the modular server by issuing an
OS command or press the POWER/SLEEP
switch. Take the modular server out of the
Module Enclosure, and install it again. Then,
press the POWER/SLEEP switch to turn on
the modular server.
8. If the same error persists, contact your
service representative.