Using the CP 1616 as a PROFINET IO Controller/Device
77
Commissioning PC Stations - Manual and Quick Start
Release 5/2005
C79000-G8976-C156-07
Follow the steps outlined below
12.
Disable the “Assign IP address via IO Controller” option.
Based on the device name, the IP address of the CP 1616 is then assigned during compilation.
13.
Once the configuration is completed, the project can be compiled and downloaded (to the PC)
with PLC
"
Download .
6.3
Example: Installing Linux Drivers (Suse Linux 9.2)
The CD “DK 16xx PN IO” contains the drivers for a Linux PC.
Follow the steps outlined below
1.
Copy the driver file “host - xxx.tar.gz” (xxx = version - specific) from the CD to any directory of
your choice.
2.
Extract the file and change to the current directory.
3.
Run the “make” command in the “/host - xxx/” path.
4.
Log on as the root user with the “su” command.
5.
Install the driver with the “make install” command.
6.
Start the driver with the “make load” command in the path of the driver.
Note
The driver can be stopped again with the “make unload” command.