beautypg.com

Siemens Commissioning PC Stations C79000-G8976-C156-07 User Manual

Page 268

background image

18

DCOM Settings with the dcomcnfg System Program

268

Commissioning PC Stations - Manual and Quick Start

Release 5/2005

C79000-G8976-C156-07

Specifying the Standard Permissions

The users that are allowed to use the OPC server must be entered in the default
access permissions, launch permissions, and configuration permissions. Several
users have been entered in the following examples of the required permissions:

Both on the server and on the client computer, the logons (and therefore the
information about permissions in the logon) must exist on the other computer.

Example: User “Alpha” is logged on at the computer with the server and “Beta” is
logged on at the computer with the client user. For DCOM operation a “Beta”
account is required on the server computer (with the same password as on the
client machine) and an “Alpha” account is required on the client computer (same
password).

The use of a group with logons is advisable when using a domain. The information
about permissions is then fetched from the domain server.

Note

The various OPC servers are implemented as services and therefore require
access permissions for the SYSTEM account.