Appendix A Cabling Information
A - 3
Table A - 1. Recommended Cable Types
Cable #
Terminating
Resistor*
-10% to +20%
Number of
Dielectric
Voltage
Ambient
Temp.
Maximum Length Cable Run
feet/meters at baud rate
and Make
Outer Dia.
1/2 Watt
Conductors/AWG
Rating
Rating
153.6s
153.6e
76.8
38.4•
(A)9823
(B)9182
(C)4596
(M)M39240
350in
8.89mm
150 ohms
2 / #22
30v
60°C
2000ft
606m
3500ft
1061m
4500ft
1364m
7500ft
2283m
(B)89182
.322in
8.18mm
150 ohms
2 / #22
150v
200°C
2000ft
606m
3500ft
1061m
4500ft
1364m
7500ft
2283m
(B)9841
(M)M3993
.270in
6.86mm
*120 ohms
2 / #24
30v
80°C
1000ft
303m
1500ft
455m
2500ft
758m
3500ft
1061m
(A)9818C
(B)9207
(M)M4270
.330in
8.38mm
100 ohms
2 / #20
300v
80°C
1500ft
455m
2500ft
758m
3500ft
1061m
6000ft
1818m
(A)9109
(B)89207
(C)4798
(M)M44270
.282in
7.16mm
100 ohms
2 / #20
150v
200°C
1500ft
455m
2500ft
758m
3500ft
1061m
6000ft
1818m
(A)9818D
(B)9815
.330in
8.38mm
100 ohms
2 / #20
1500ft
455m
2500ft
758m
3500ft
1061m
6000ft
1818m
(A)9818
(B)9855
(M)M4230
.315in
8.00mm
100 ohms
4 (two pair) #22
150v
60°C
1200ft
364m
1700ft
516m
3000ft
909m
4500ft
1364m
(A)9110
(B)89696
(B)89855
(M)M64230
.274in
6.96mm
100 ohms
4 (two pair) #22
150v
200°C
1200ft
364m
1700ft
516m
3000ft
909m
4500ft
1364m
(A)9814C)
(B)9463
(M)M4154
.243in
6.17mm
75 ohms
2 / #20
150v
60°C
800ft
242m
1500ft
455m
2500ft
758m
3500ft
1061m
(A)5902C
(B)9302
(M)M17002
.244in
6.20mm
75 ohms
4 (two pair) #22
300v
80°C
200ft
60m
500ft
152m
1200ft
333m
2500ft
758m
Notes:
A = Alpha, B = Belden, C = Consolidated, M = Manhattan
• = Limited to 16 taps at 38.4 Kbaud