Drive Duty and Carrier Frequency Selection: C6-01 and C6-02

n

Drive Duty Selection: C6-01

The drive has two different duty modes from which to select based on the load characteristics.

The drive rated current, overload capacity, and carrier frequency will change depending upon

the duty mode selection. Use parameter C6-01 (Duty Cycle) to select Heavy Duty (HD) or

Normal Duty (ND) for the application. The default setting is ND.

Refer to Specifications on

page 199

for details about the rated current.

HD and ND Mode Selections

Mode

HD Rating

ND Rating

C6-01

0

1

Characteristics

100 %

100 %

0

Motor Speed

Rated Load

Overload

150 %

Motor Speed

0

100 %

100 %

120 %

Rated Load

Overload

Application

Use HD Rating is designed applications

requiring a high overload tolerance with

constant load torque, like conveyors.

Use ND Rating for applications in which the

torque requirements drop along with the speed.

Examples include fans or pumps where a high

overload tolerance is not required.

Overload capability

(oL2)

100% continuous, 150% of drive rated current

for 60 s

100% continuous, 120% of drive rated current

for 60 s

C6-02

2.0 to 15.0 kHz (default depends on drive capacity)

L3-02 Stall

Prevention during

Acceleration

150%

120%

L3-06 Stall

Prevention during

Run

150%

120%

Note:

1. By selecting HD/ND, motor parameter E2 is changed to the value for the maximum applicable

motor.

2. Swing PWM uses 2.0 kHz carrier frequency as a base. The application of special PWM patterns

keeps the audible noise of the motor low.