H1 Multi-Function Digital Input Selections
H1-
Setting
Function
Description
Page
0
3-Wire Sequence
Closed: Reverse rotation (only if the drive is set up for 3-Wire
sequence)
–
1
LOCAL/REMOTE Selection
Open: REMOTE, Run and frequency reference source set in
b1-01/02
Closed: LOCAL, LED operator is run and reference source
–
2
Serial Communication
Reference Selection
Open: REMOTE, Run and frequency reference source set in
b1-01/02
Closed: MEMOBUS/Modbus Communication
–
3
Multi-Step Speed Reference 1
Used to select Multi-Step Speeds set in d1-01 to d1-08
–
4
Multi-Step Speed Reference 2
–
5
Multi-Step Speed Reference 3
–
6
Jog Reference Selection
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority over
all other reference sources.
–
7
Accel/Decel Time 1
Used to switch between Accel/Decel Time 1 and 2
–
8
Baseblock Command (N.O.)
Open: Normal operation
Closed: No drive output
–
9
Baseblock Command (N.C.)
Open: No drive output
Closed: Normal operation
–
A
Accel/Decel Ramp Hold
Closed: The drive pauses during acceleration or deceleration
and maintains the output frequency.
–
F
Not used
Select this setting when not using the terminal or when using
the terminal in a pass-through mode.
–
10
Up Command
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference.
Ensure that the increase and decrease commands are set in
conjunction with one another.
–
11
Down Command
–
14
Fault Reset
Closed: Resets faults if the cause is cleared and the Run
command is removed.
–
15
Fast-Stop (N.O.)
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run must
be cycled.
–
17
Fast-stop (N.C.)
Open: Decelerates according to C1-09 (Fast-stop Time)
–