beautypg.com

Motor hunting and oscillation control parameters, 2 motor performance fine tuning – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 126

background image

u

Motor Hunting and Oscillation Control Parameters

The following parameters indirectly affect motor hunting and oscillation.

Table 5.2 Parameters that Affect Control Performance in Applications

Name (Parameter No.)

Application

Accel/Decel Time (C1-01

through C1-09)

Adjusting accel and decel times will affect the torque presented to the motor during

acceleration or deceleration.

S-Curve Characteristics

(C2-01 through C2-04)

Prevents shock at the beginning and end of acceleration and deceleration.

Jump Frequency (d3-01

through d3-04)

Skips over the resonant frequencies of connected machinery.

Analog Filter Time Constant

(H3-13)

Prevents fluctuation in the analog input signal due to noise.

Stall Prevention (L3-01

through L3-06)

• Prevents motor speed loss and overvoltage. Used when the load is too heavy and

also during sudden acceleration/deceleration.

• Adjustment is not normally required because Stall Prevention is enabled as a

default. Disable Stall Prevention during deceleration (L3-04 = “0”) when using

a braking resistor.

5.2 Motor Performance Fine Tuning

126

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide