12 wiring checklist – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 67

3.12 Wiring Checklist
No.
Item
Page
Drive, peripherals, option cards
1
Check drive model number to ensure receipt of correct model.
2
Check for correct braking resistors, DC link chokes, noise filters, and other peripheral
devices.
Installation area and physical setup
3
Ensure area surrounding the drive complies with specifications.
Power supply voltage, output voltage
4
The voltage from the power supply should fall within the input voltage specification range
of the drive.
5
The voltage rating for the motor should match the drive output specifications.
Main circuit wiring
6
Confirm proper branch circuit protection exists per National and Local codes.
7
Properly wire the power supply to drive terminals R/L1, S/L2 and T/L3.
8
Properly wire the drive and motor together. The motor lines and drive output terminals
R/T1, V/T2 and W/T3 should match in order to produce the desired phase order. If the
phase order is incorrect, the drive will rotate in the opposite direction.
9
Use 600 Vac vinyl-sheathed wire for the power supply and motor lines.
10
Use the correct wire gauges for the main circuit. Refer to
through
.
• When using comparatively long motor cable, calculate the amount of voltage drop.
3 x voltage resistance (Ω/km) x cable length (m) x motor rated current (A) x 10
-3
Motor rated voltage (V) x 0.02 ≥
• If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency
(C6-02) accordingly.
11
Properly ground the drive. Review page
.
12
Tightly fasten all terminal screws (control circuit terminals, grounding terminals). Refer
..
3.12 Wiring Checklist
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide
67
3
Electrical Installation