B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 230

No.
Name
Description
Range Def. Mode Addr.
Hex
Pg.
L3-01
Stall
Prevention
Selection
during
Acceleration
Selects the Stall Prevention method used to prevent
excessive current during acceleration.
0: Disabled - Motor accelerates at active acceleration
rate. The motor may stall if load is too heavy or accel
time is too short.
1: General Purpose - When output current exceeds
L3-02 level, acceleration stops. Acceleration will
continue when the output current level falls below the
L3-02 level.
0, 1
<1>
1
O
48F
–
L3-02
Stall
Prevention
Level during
Acceleration
Used when L3-01 = 1.
100% is equal to the drive rated current.
Decrease the set value if stalling or excessive current
occurs with default setting.
0 to 150
<4>
<2>
<4>
O
490
–
L3-04
Stall
Prevention
Selection
during
Deceleration
When using a braking resistor, use setting "0".
0: Disabled - The drive decelerates at the active
deceleration rate. If the load is too large or the
deceleration time is too short, an ov fault may occur.
1: General Purpose - The drive decelerates at the
active deceleration rate, but if the main circuit DC bus
voltage reaches the Stall Prevention level,
deceleration will stop. Deceleration will continue
once the DC bus level drops below the Stall
Prevention level.
4: Overexcitation Deceleration - Decelerates with the
flux level determined by n3-13 (Overexcitation
Gain).
0, 1, 4
1
S
492
–
L3-05
Stall
Prevention
Selection
during Run
Selects the Stall Prevention method to use to prevent
drive faults during run.
0: Disabled - Drive runs a set frequency. A heavy load
may cause the drive to trip on an oC or oL fault.
1: Decel Time 1 - The drive will decelerate at Decel
Time 1 (C1-02) if the output current exceeds the level
set by L3-06. Once the current level drops below the
L3-06 level, the drive will accelerate back to its
frequency reference at the active acceleration rate.
2: Decel Time 2 - Same as setting 1 except the drive
decelerates at Decel Time 2 (C1-04).
When output frequency is 6 Hz or less, Stall
Prevention during run is disabled regardless of the
setting in L3-05.
0 to 2
1
O
493
–
L3-06
Stall
Prevention
Level during
Run
Enabled when L3-05 is set to "1" or "2". 100% is
equal to the drive rated current.
Decrease the set value if stalling or excessive current
occurs with the default settings.
Upper level is determined by C6-01 and L8-38.
30 to
150
<4>
<2>
<4>
O
494
–
L4: Frequency Detection
Use L4 parameters to configure frequency detection operation.
L4-01
Speed
Agreement
Detection
Level
These parameters configure the multi-function output
(H2- 01 = 2, 4, 5) settings "Speed Agree 1",
"Frequency Detection 1," and "Frequency detection
2".
0.0 to
400.0
0.0
Hz
O
499
–
B.2 Parameter Table