H1 Multi-Function Digital Input Selections

H1-

Setting

Function

Description

Page

20 to 2F External Fault

20: N.O., Always Detected, Ramp To Stop

21: N.C., Always Detected, Ramp To Stop

22: N.O., During Run, Ramp To Stop

23: N.C., During Run, Ramp To Stop

24: N.O., Always Detected, Coast To Stop

25: N.C., Always Detected, Coast To Stop

26: N.O., During Run, Coast To Stop

27: N.C., During Run, Coast To Stop

28: N.O., Always Detected, Fast-stop

29: N.C., Always Detected, Fast-stop

2A: N.O., During Run, Fast-stop

2B: N.C., During Run, Fast-stop

2C: N.O., Always Detected, Alarm Only (continue running)

2D: N.C., Always Detected, Alarm Only (continue running)

2E: N.O., During Run, Alarm Only (continue running)

2F: N.C., During Run, Alarm Only (continue running)

40

Forward Run Command

(2-Wire sequence)

Open: Stop

Closed: Forward run

41

Reverse Run Command

(2-Wire sequence)

Open: Stop

Closed: Reverse run

61

External Search Command 1

Closed: Activates Current Detection Speed Search from the

max. output frequency (E1-04)

62

External Search Command 2

Closed: Activates Current Detection Speed Search from the

frequency reference

67

Communications Test Mode

Tests the MEMOBUS/Modbus RS-422/485 interface.

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

H2: Multi-Function Digital Output MA-MB-MC

Use H2 parameters to assign functions to the multi-function digital output MA-MB-MC.

H2-01

Terminal MA,

MB and MC

Function

Selection

(relay)

Refer to H2 Multi-Function Digital Output Settings

on page

225

for a description of setting values.

0 to 13D

E

O

40B

105

H2 Multi-Function Digital Output Settings

H2-01

Setting

Function

Description

Page

0

During Run

Closed: A Run command is active or voltage is output

1

Zero Speed

Closed: Output frequency is 0

2

Speed Agree 1

Closed: Output frequency equals the speed reference (plus or

minus 2 Hz hysteresis)

4

Frequency Detection 1

Closed: Output frequency is less than or equal to the value in

L4-01 with 2 Hz hysteresis

B.2 Parameter Table

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

225

B

Parameter List