Table c.9, Are yaskawa, C.3 ul standards – Yaskawa J1000 Compact V/f Control Drive User Manual
Page 256

Drive
Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw Size
Tightening
Torque
N•m (lb.in.)
2A0012
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
2A0020
R/L1, S/L2, T/L3
10
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
Table C.9 Wire Gauge and Torque Specifications
Drive
Model
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw Size
Tightening
Torque
N•m (lb.in.)
4A0001
4A0002
4A0004
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
14
14 to 10
4A0005
4A0007
4A0009
R/L1, S/L2, T/L3
14
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
4A0011
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
Note:
Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a
continuous maximum allowable temperature of 75 °C 600 V UL approved vinyl sheathed insulation.
Ambient temperature should not exceed 30 °C.
C.3 UL Standards
256
YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide